ARDP intelligent water pump controller

1 Overview

The ARDP intelligent water pump controller is suitable for low-voltage systems and is a new generation intelligent integrated device for protection, monitoring and control of feeder terminals of low-voltage motors. This product integrates measurement, protection, control, and bus communication. It replaces various protection relays, power meters, switches, buttons, and signal indicators that are configured with separate components. It integrates a variety of control methods into one. At the same time, it also provides records of important management information such as the number of operations, running time, and tripping events. The bus communication function can exchange data with servers or workstations on the network. It is an ideal choice for factory automation and building intelligence.

2 smart water pump controller

AC sampling measurements are used to measure the changing voltage/current values. All data for each phase is sampled at a rate of 3.2 KHz, integrated over the period, and the root mean square value is calculated. Integrated with various types of protection and control functions, it can be widely used in deep well pumps, submersible pumps, centrifugal pumps, sewage pumps, pipeline pumps, booster pumps, and multi-stage pumps.

2.1 Product Features

â—† Three-phase voltage two-phase three-phase current loop AC sampling, true RMS calculation

â—† Water Level Detection Support Float Level Detector, Reed-type Liquid Level Detector, Level Transmitter

â—†Manual/Automatic mode switching: manual/automatic operation of one pump, manual/automatic operation of two pumps (one main and two standby, two main and one standby, two pump operations (alternate alternate preparation)), and two pumps (independent) manual /automatic running

â—† High water level control: One pump in the middle water level runs, and two water pumps in the high water level run simultaneously.

â—†Integrate 2 independent timers with timed pump activation.

â—† Integrated PC software, easy to set up and debug

â—†AC/DC power supply

2.2 Protection Features

â—†Overvoltage/undervoltage protection

â—†Phase protection

â—† start overtime protection

â—† overload / underload (dry) protection

â—†Failure protection

â—† Ground protection

â—† Blocking/blocking protection

â—†Short circuit protection

â—†Unbalance protection

â—† External fault protection

2.3 Related standards

● GB/T17626.4-2006 electrical fast transient burst immunity test

● GB/T17626.5-2006 surge (impact) immunity test

3 Product Models and Specifications

Table 1

Note: The controller measurement allows 8 times overload, that is, 100A specification can measure current of 800A and current input signal of 100A/20mA.

Table 2

Note: 1. It is necessary to separately purchase single-phase or three-phase (integral) transformers for use with the controller. The transformer size is 100A/20mA.

2. When the SR function is selected, the controller supports two control outputs with time setting (this time before the factory setting or optional C function, set by the host computer software).

3, optional float level sensor, reed-type liquid level sensor, liquid level transmitter, leakage protection relay.

4 Technical Specifications

table 3

Technical Parameters

Technical indicators

Controller auxiliary power

AC85V~265V/DC100V~350V

Rated operating voltage of the motor

AC220/380V, 50Hz

Rated operating current of the motor

1 A (0.1A-9999A)

Small dedicated current transformer

5A (0.1A-9999A)

1.6A (0.4A-1.6A)

6.3A (1.6A-6.3A)

25A (6.3A-25A)

100A(25A-100A)

Relay output contacts, rated load capacity

6-way control relay: AC250V, 3A/DC30V, 3A

Switch input

6 way, optical isolation

Level signal input

Float switch, reed-type level switch or liquid level transmitter

communication

RS485 Modbus protocol

SOE event recording capacity

8 event records

Pollution level

2

Protection level

Panel IP54

5 Dimensions and Installation
5.1 Controller Installation Dimensions (Unit: mm)

5.2 Current Transformer Installation Dimensions (Unit: mm)

● Three-phase current transformer installation dimension drawing (unit: mm)

● Single-phase current transformer installation dimension drawing (unit: mm)

6 Two pumps direct start wiring diagram

1, the water level signal can choose 1 (float ball) water level switch, 2 water level switch, 3 water level switch, water level transmitter, for the small size of the pool, start and stop the liquid level difference can choose 2 water level switch, access to high water level and Low water level input terminals (signal requirements: closed signal at high water level and low water level).

2, when the water level signal is selected as 1 (float ball) water level switch, when the water supply application mainly detects high water level signal (ie, high water level is closed), the low water level can be closed and connected to the low water level input terminal. When both lights are on, it means that the float The ball sensor is damaged. When the drainage application mainly detects the low water level signal (that is, the low water level is closed), the high water level can be closed and connected to the high water level input terminal. When both lights are on, the float sensor is damaged.

3. When dry-reed level switches are used, three normally-opened reed switches are used to connect high-, mid-, and low-level terminals respectively. When two pumps discharge water automatically, one pump automatically starts when the controller detects the middle water level. When a high water level signal is detected, the second water pump starts automatically. When a low water level is detected, both pumps stop. The control logic is reversed for water supply applications.

4. When the pressure control is used in water supply applications, the float low water level close signal is connected to the low water level terminal for the pool empty detection.

5. The default level transmitter is two-wire (+15V output and 4-20mA input). If it is other signals, special instructions are required when ordering. Two pumps are in automatic mode. One pump controls the height and one pump starts. When the two controls the height, the two pumps start at the same time.

7 level drainage application example

Starting conditions: When a pump is used, the liquid level is higher than the high water level. Two pumps, drainage pump mode (one main two, two main and one standby, two pumps running) and the water level signal is 3 water level switch. When the liquid level is higher than the neutral water level, a water pump starts and the liquid level is higher than the high water level. At the point, the second pump starts.

Shutdown conditions: The liquid level is lower than the low water level.

Note: When draining the two pumps, two levels of liquid level signals are used to control the two pumps independently.

8 plan on the map