Model NO.: GW1
Number of Poles: Three Pole
Grounding: Single Ground
Series: Single-Stage
Run: Vertical Rotation
Switching Mode: Single Throw-in
Structure of Operating: Manual
Certification: ISO
Trademark: HEMG
Transport Package: Carton with Wooden
Specification: 15KV/27KV/38KV, 50HZ/60HZ,
Origin: China
Model NO.: GW1
Number of Poles: Three Pole
Grounding: Single Ground
Series: Single-Stage
Run: Vertical Rotation
Switching Mode: Single Throw-in
Structure of Operating: Manual
Certification: ISO
Trademark: HEMG
Transport Package: Carton with Wooden
Specification: 15KV/27KV/38KV, 50HZ/60HZ,
Origin: China
 Â
1Â General
   GW1-35 Outdoor high voltage separation relationship outdoor installation general purpose isolating switch. Forthree-phase alternating current 50Hz. Rated voltage 12KV and below the power system. The circuit is switched on when there is a voltage without a negative voltage.. The product is in line with the GB1985 "AC high voltage isolation switch and grounding switch". DL486 order "technical conditions for AC high voltage isolating switch,The national standard DL/T593 "high voltage isolation switch equipment common order technical conditions" and the power industry standard.  Â
2Â Using environmental conditions.
2.1 altitude 3000M.
2.2 ambient temperature is -25 degrees C to +40.
2.3 wind pressure is not more than 700Pa.
2.4 ice thickness is not more than 1mm.
2.5 earthquake intensity is not more than 8 degrees.
2.6 the installation site should have no regular violent vibration and flammable. Effect of explosive material and chemical corrosion.
3Â Product model
 G W 1-35 D W /630-
25
Effective value of 4S thermal stable current (KA)
Rated current (A)
Anti fouling type (without this symbol for the common type)
 With earth switch (without the sign without grounding switch)
                        D1 is a moving contact ground, and D2 is a static contact ground.
                    Â
                         Rated voltage(KV)
                         Design number
                         Outdoor high voltage isolating switch
Â
Â
Â
4Â Model specifications and technical parameters
Serial number | Â Â Â Project | Model specification | ||||||
630A |
630 A D |
3150A |
3150A D |
4000A |
4000A D |
|||
1 | Rated voltage(kV) | 35 | 35 | 35 | 35 | 35 | 35 | |
2 | Maximum operating voltage(kV) | 40.5 | 40.5 | 40.5 | 40.5 | 40.5 | 40.5 | |
3 | Rated current(A) | 630 | 630 | 3150 | 3150 | 4000 | 4000 | |
4 | 4S short-time withstand current(kA) | 25 | 25 | 31.5 | 31.5 | 31.5 | 31.5 | |
5 | Rated peak withstand current(kA) | 63 | 63 | 80 | 80 | 80 | 80 | |
6 | 1minEffective value of power frequency withstand voltage | On the ground | 42 | 42 | 42 | 42 | 42 | 42 |
Fracture | 48 | 48 | 48 | 48 | 48 | 48 |
5 Structure principle
5.1GW1 - 35 switch outline and installation dimensions are shown in Figure 2.
GW1 - 35 for single phase structure. Each phase consists of a chassis, the main knife (ground knife), movable contact head, static contact head, shaft, rod insulators. Three-phase through a connecting pipe is connected, the operation shaft with rod insulators to drive the main knife switch, touch knife with trough outline form, increased mechanical strength and heat dissipation area.
5.2Â GW1-35D -switch is a kind of switch on the GW1 - 35 to add a ground knife.
Equipped with CS6-2 operating mechanism after the, can achieve the main knife switch, knife cannot contract; knife switch, the surgeon can not closing the anti error interlocking requirements.
5.3Â GW1 - 35 switch with CS6-2 mechanism (see Figure 1).
6 Installation and adjustment
6.1Â GW1 - 35 in the installation site for three - phase connection and the operation of the motivation structure. Installation diagram see Figure 3. The 2 switch based 10 channel as channel and switch bottom mounting frame.
Vertical arrangement of frame. To adjust in the following order.
6.2 The switch is arranged on the foundation (the main contact cutter and the grounding knife in the closing state) adjust three-phase coaxial switch. 3/4 water gas pipe three switch welding connection.Then Switch fixed.
6.3Â The handle of the mechanism is arranged in the same position with the switch of the switch. The crank arm is welded to the water gas pipe. Attention should be paid to the welding angle and length of the crank arm. GW1 - 35 switch principal axis welding long crank arm L = 120,W1 - 35 switch,The main knife shaft welding arm L = 120mm, grounding knife shaft welding arm L = 120mm. according to the size of welding rod installation.
6.4 Connecting the switch and the actuating mechanism with the connecting rod. Three-phase synchronization inching switch, the three phase is less than or equal to 3mm.
6.5 Switch installation adjustment is completed. Operation 20 times to check parts is loose, three-phase synchronization changes, the earthing switch is closing in place, operating mechanism can reach the designated position and lock.
6.6 After installation and adjustment, according to the following acceptance of the project.
Â
Serial numbe  | Acceptance content    | technical requirement | |
1 | Appearance | Testing | Rust proof. The switch name brand is correct, the position is correct. The fastening part of the fastener without loosening, and ensure the verticality and shaft coaxial switch. |
2 | Spring pressure | 630A | 431±39N |
 1250A 3150A | 441±44 | ||
3 | The main knife fracture distance | ≥360mm | |
4 | Ground knife fracture distance (on the ground) | ≥360mm | |
5 | The main switch three phase | ≤5mm | |
6 | Operating torque | The main knife | ≤300N·M |
The grounding knife | ≤300N·M | ||
7 | The surgeon and the knife body chain | Don't switch on the main knife knife switch, knife knife not closing closing. | |
8 | Switching operations | The operation is flexible, convenient and accurate. Check pin down hole correctly. The main and the ground knife can be divided into place. |
 7.1 Before putting into operation, the contact parts of the conductor should be in good contact with each other. Switch and bus connection should be reliable. The moving parts should be flexible.
 7. 2 Operation: the switch must be cut off before the line can be operated.
 7.3 Switch shall be carried out for 12 times a year, and the following items should be paid attention to during the overhaul:
 7.3.1 Check the stability of the structure and the connection is reliable.
 7.3.2 Maintenance of conductor contact surface is in contact with the surface coated with neutral vaseline.
 7.3.3 Replace damaged parts.
 8 Acceptance and storage
 8.1 Acceptance: the product arrives at the destination, should as soon as possible to check out of the box. Check the product model specifications according to the order contract. According to the packing list and check random file attachments. Check whether the product is damaged. If the abnormal phenomenon is found, please inform the manufacturer in time.
 8.2 Storage: the product out of the box, if not immediately installed, should be kept in a shelter and clean ventilation.
Â
 9 Order notice
 9.1 When ordering, please fill in the type, specification, name, quantity and basic technical parameters of the product,
 9.2 Special requirements for products must be specified.        Â
Â
Â
Â
Â
Â
Â
Â
Â
Â
Â
 Â
Â
1Â General
   GW1-35 Outdoor high voltage separation relationship outdoor installation general purpose isolating switch. Forthree-phase alternating current 50Hz. Rated voltage 12KV and below the power system. The circuit is switched on when there is a voltage without a negative voltage.. The product is in line with the GB1985 "AC high voltage isolation switch and grounding switch". DL486 order "technical conditions for AC high voltage isolating switch,The national standard DL/T593 "high voltage isolation switch equipment common order technical conditions" and the power industry standard.  Â
2Â Using environmental conditions.
2.1 altitude 3000M.
2.2 ambient temperature is -25 degrees C to +40.
2.3 wind pressure is not more than 700Pa.
2.4 ice thickness is not more than 1mm.
2.5 earthquake intensity is not more than 8 degrees.
2.6 the installation site should have no regular violent vibration and flammable. Effect of explosive material and chemical corrosion.
3Â Product model
 G W 1-35 D W /630-
25
Effective value of 4S thermal stable current (KA)
Rated current (A)
Anti fouling type (without this symbol for the common type)
 With earth switch (without the sign without grounding switch)
                        D1 is a moving contact ground, and D2 is a static contact ground.
                    Â
                         Rated voltage(KV)
                         Design number
                         Outdoor high voltage isolating switch
Â
Â
Â
4Â Model specifications and technical parameters
Serial number | Â Â Â Project | Model specification | ||||||
630A |
630 A D |
3150A |
3150A D |
4000A |
4000A D |
|||
1 | Rated voltage(kV) | 35 | 35 | 35 | 35 | 35 | 35 | |
2 | Maximum operating voltage(kV) | 40.5 | 40.5 | 40.5 | 40.5 | 40.5 | 40.5 | |
3 | Rated current(A) | 630 | 630 | 3150 | 3150 | 4000 | 4000 | |
4 | 4S short-time withstand current(kA) | 25 | 25 | 31.5 | 31.5 | 31.5 | 31.5 | |
5 | Rated peak withstand current(kA) | 63 | 63 | 80 | 80 | 80 | 80 | |
6 | 1minEffective value of power frequency withstand voltage | On the ground | 42 | 42 | 42 | 42 | 42 | 42 |
Fracture | 48 | 48 | 48 | 48 | 48 | 48 |
5 Structure principle
5.1GW1 - 35 switch outline and installation dimensions are shown in Figure 2.
GW1 - 35 for single phase structure. Each phase consists of a chassis, the main knife (ground knife), movable contact head, static contact head, shaft, rod insulators. Three-phase through a connecting pipe is connected, the operation shaft with rod insulators to drive the main knife switch, touch knife with trough outline form, increased mechanical strength and heat dissipation area.
5.2Â GW1-35D -switch is a kind of switch on the GW1 - 35 to add a ground knife.
Equipped with CS6-2 operating mechanism after the, can achieve the main knife switch, knife cannot contract; knife switch, the surgeon can not closing the anti error interlocking requirements.
5.3Â GW1 - 35 switch with CS6-2 mechanism (see Figure 1).
6 Installation and adjustment
6.1Â GW1 - 35 in the installation site for three - phase connection and the operation of the motivation structure. Installation diagram see Figure 3. The 2 switch based 10 channel as channel and switch bottom mounting frame.
Vertical arrangement of frame. To adjust in the following order.
6.2 The switch is arranged on the foundation (the main contact cutter and the grounding knife in the closing state) adjust three-phase coaxial switch. 3/4 water gas pipe three switch welding connection.Then Switch fixed.
6.3Â The handle of the mechanism is arranged in the same position with the switch of the switch. The crank arm is welded to the water gas pipe. Attention should be paid to the welding angle and length of the crank arm. GW1 - 35 switch principal axis welding long crank arm L = 120,W1 - 35 switch,The main knife shaft welding arm L = 120mm, grounding knife shaft welding arm L = 120mm. according to the size of welding rod installation.
6.4 Connecting the switch and the actuating mechanism with the connecting rod. Three-phase synchronization inching switch, the three phase is less than or equal to 3mm.
6.5 Switch installation adjustment is completed. Operation 20 times to check parts is loose, three-phase synchronization changes, the earthing switch is closing in place, operating mechanism can reach the designated position and lock.
6.6 After installation and adjustment, according to the following acceptance of the project.
Â
Serial numbe  | Acceptance content    | technical requirement | |
1 | Appearance | Testing | Rust proof. The switch name brand is correct, the position is correct. The fastening part of the fastener without loosening, and ensure the verticality and shaft coaxial switch. |
2 | Spring pressure | 630A | 431±39N |
 1250A 3150A |