High voltage circuit breaker test selection scheme

Insulation resistance

cycle Claim Description





1) 1 to 3 years

2) After overhaul

1) The overall insulation resistance is self-regulated

2) The insulation resistance of the lifting rod made of fracture and organic matter should not be lower than the following table: MΩ






Use 2500V megohmmeter

Test category

Rated voltage kV

<24

24~40.5

72.5~252

363

1000

2500

5000

10000

1000

2500

5000

10000

Capacitance and tgδ of tgδ-arc chamber shunt capacitors for 40.5kV and above non-pure casing and multi-oil circuit breakers

cycle Claim Description


1) 1 to 3 years

2) After overhaul

1) Non-pure porcelain casing tgδ (%) value inspection casing section of multi-oil circuit breaker at 20 °C;

2) The tgδ(%) value of the impure porcelain casing circuit breaker at 20 °C can be increased by the following values ​​compared to the corresponding tgδ(%) value in the casing section:



1) Measure each bushing in the open state. When the measured tgδ exceeds the specified value or there is a significant increase, the tank must be dropped for the decomposition test. For circuit breakers that cannot drop the fuel tank, the oil should be released from the rent, so that the lower part of the casing and the arc extinguishing chamber are exposed to the oil surface, and then the partial pressure test is carried out.

2) When the circuit breaker is overhauled and the casing is not overhauled, it should be increased according to the corresponding value specified in the casing operation.

3) The overall tgδ(%) with shunt resistor breaker can be increased accordingly

Rated voltage
(kV)

≥126

<126

40.5 (DW1-35DW1-35D)

The increase in the value of tgδ(%)

1

2

3

AC withstand voltage test of lifting rods for oil circuit breakers of 126kV and above

cycle Claim Description


1) After overhaul

2) When necessary



Test voltage is 80% of the value specified in DL/T593

1) Pressure-resistant equipment can not meet the requirements of time segmentation
In progress, the number of segments should not exceed 6 segments (252kV).
Or three segments (126kV), pressurization time is 5min

2) Each test voltage can take the entire test voltage value
Divided by 1.2 times the value obtained by the number of segments or self-regulated

Circuit breaker grounding, fracture and phase AC withstand voltage test

cycle Claim Description



1) 1 to 3 years (12kV and below)

2) After overhaul

3) When necessary (72.5kV and above)

The circuit breakers are separately operated in the divided and closed states. The test transformer values ​​are as follows:

The 12~40.5kV circuit breaker is grounded and phased according to the specified value of DL/T593;

80% of the value specified in DL/T593 for 72.5kV and above




For the three-phase common-box type oil circuit breaker, the phase-to-phase withstand voltage should be used, and the test voltage value is the same as the ground pressure resistance value.

Conductive loop resistance

cycle Claim Description

1) 1 to 3 years

2) After overhaul

1) After the overhaul, it should meet the manufacturer's regulations.

2) Self-regulation during operation


Measured by DC voltage drop method, current is not less than 100A

Circuit breaker time parameter

cycle Claim

1) After overhaul

2) After the institution is overhauled

Unless otherwise specified by the manufacturer, the circuit breaker's division and closing synchronicity shall meet the following requirements:

The phase closure is not more than 5ms in different periods;

The phase between the phases is not more than 3ms;

Closing between the same phase breaks is not more than 3ms;

The different periods between the fractures of the same phase are not more than 2ms;

Speed ​​characteristics of circuit breakers

cycle Claim Description

After overhaul

Should comply with manufacturer regulations

Under rated operating voltage (air pressure, hydraulic pressure)

DC resistance of the brake coil

cycle Claim

After overhaul

DC resistance should comply with manufacturer's regulations

Leakage current of 40.5kV and above oil-less circuit breakers

cycle Claim Description



1) 1 to 3 years

2) After overhaul

1) The test voltage of each component is as follows:





252kV and above oil-less circuit breaker lifting rods (including
When the leakage current of the supporting porcelain sleeve is greater than 5μA,
Attention

Rated voltage kV

40.5

72.5~252

≥363

DC test voltage kV

20

40

60

2) The leakage current is generally not more than 10μA

Vacuum switch vacuum interrupter vacuum measurement

cycle Claim Description

Big and small repair time

Self-regulation

When conditions permit

Stereo Headphones

Stereo headphone is important components of audio equipment. It has a wide frequency response, low distortion, power saving, strong audio resolution, clear surround sound, and good music rhythm. Stereo headphone is divided into earphone and headphone, which has the difference of left and right channels. It cannot be used interchangeably. Otherwise, the fidelity of the sound source and the resolution of the source frequency will be directly affected.

Stereo Headphones

Stereo Headphones,Wireless Stereo Headphones,Bluetooth Stereo Headphones,Wireless Bluetooth Stereo Headphones

Shenzhen Linx Technology Co., Ltd. , https://www.linxheadphone.com

Posted on