Sv8 (VS1) -12 Series Embedded Poles Type Indoor Circuit Breaker

Model NO.: SV8(VS1)-12
Function: Circuit-Breaker Failure Protection
Certification: CE
Rated Voltage: 3.6kv~40.5kv
Rated Short-Circuit Breaking Current: 20/25ka 31.5ka 40ka
Rated Current: 630/1250A 630/1600A
Mechanical Life: 10000times
Rated Thermal Stability of Current: 20/25ka 31.5ka 40
Dynamic Stability Rated Current(Peak): 63ka 80ka 100
Rated Short-Circuit Closing Current(Peak: 63ka 80ka 100
Rated Operating Sequence: 0-0.3s-Co-180s-Co
Rated Thermal Stabilization Time: 4s
Transport Package: Standard Export Carton
Specification: CE
Origin: China
SV8(VS1)-12 Series Embedded Poles Type Indoor High Voltage Vacuum Circuit Breaker
SV8(VS1)-12 Series Embedded Poles Type Indoor High Voltage Vacuum Circuit Breaker
rated voltage 12kV
rated short-circuit breaking current 20/25kA        31.5kA             40kA
rated current 630/1250A   630 1250    1250 1600
                      1600 2000  2000 2500
                       2500 3150       3150
rated thermal stability of current 20/25kA        31.5kA              40
dynamic stability rated current(peak) 63kA              80kA              100
rated short-circuit closing current(peak) 63kA              80kA               100
rated short-circuit breaking current breaking number 50times
frequency tolerance of the secondary circuit voltage(1min) 2000V
rated operating sequence 0-0.3s-CO-180s-CO
rated thermal stabilization time 4S
rated a single/back-to-back electric current breaking device group 630/400A  800/400A(40kA)
mechanical life 10000Times
NO Item Unit Technical Data
1 Rated voltage KV 12
2 1 min power frequency withstand voltage 42
Lighting impulse withstand voltage(peak value) 75
3 Rated Frequency Hz 50
4 Rated current A 630, 1250, 1600, 2000, 2500, 3150, 4000
5 Rated short time withstand current KA 20, 25, 31.5, 40
6 Rated withstand current(peak) 50, 63, 80, 100
7 Rated short-circuit opening current 20, 25, 31.5, 420
8 Rated short-circuit closing current 50, 63, 80, 100
9 Rated duration of short-circuit S 4
10 Contact's clearance    3.5±0.5
11 Contact's travel    9±1/11±1
12 Average opening speed M/s 1.1±0.2
13 Average closing speed M/s 0.6±0.2
14 Opening time Ms 35-60
15 Closing time Ms 20-45
16 Mechanical life Times 30000
17 Rated operating order    O-0.3S-CO-180S-CO(<40KA)
O-180S-CO-180S-CO(≥40KA)

The GFCI will not protect you from line contact hazards (i.e. a person holding two "hot" wires, a hot and a neutral wire in each hand, or contacting an overhead power line). However, it protects against the most common form of electrical shock hazard, the ground-fault. It also protects against fires, overheating, and destruction of wire insulation.